Underground Gland Sizes to Suit SWA Cable | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Cable size | Number of Cores | |||||||||||
(mm) | 1 | 2 | 3 | 4 | 5 | 7 | 10 | 12 | 19 | 27 | 37 | 48 |
1.5 | - | - | BW20S | BW20S | BW20S | BW20 | BW20 | BW25 | BW25 | BW32 | BW32 | |
2.5 | - | BW20S | BW20S | BW20S | BW20S | BW20 | BW25 | BW25 | BW25 | BW32 | BW32 | BW40 |
4 | - | BW20S | BW20S | BW20 | BW25 | BW25 | BW25 | BW25 | BW32 | BW40 | - | - |
6 | - | BW20 | BW20 | BW20 | - | - | - | - | - | - | - | - |
10 | - | BW20 | BW20 | BW25 | - | - | - | - | - | - | - | - |
16 | - | BW25 | BW25 | BW25 | - | - | - | - | - | - | - | - |
25 | - | BW25 | BW32 | BW32 | - | - | - | - | - | - | - | - |
35 | - | BW32 | BW32 | BW32 | - | - | - | - | - | - | - | - |
50 | BW25 | BW32 | BW32 | BW32 | - | - | - | - | - | - | - | - |
70 | BW25 | BW32 | BW40 | BW40 | - | - | - | - | - | - | - | - |
95 | BW25 | BW40 | BW40 | BW50 | - | - | - | - | - | - | - | - |
120 | BW25 | BW40 | BW50 | BW50 | - | - | - | - | - | - | - | - |
150 | BW32 | BW40 | BW50 | BW50 | - | - | - | - | - | - | - | - |
185 | BW32 | BW50 | BW50 | BW63 | - | - | - | - | - | - | - | - |
240 | BW40 | BW50 | BW63 | BW63 | - | - | - | - | - | - | - | - |
300 | BW40 | BW63 | BW63 | BW75 | - | - | - | - | - | - | - | - |
400 | BW50 | BW63 | BW75 | BW75 | - | - | - | - | - | - | - | - |